Product Description
Envirograf Surface Mounted Intumescent Fire & Smoke Seals are surface-mounted intumescent fire or fire and smoke seals providing up to 1 hour fire protection, available in a range of colours and wood veneer finishes. Supplied as a pack with intumescent paper for use around lock and hinge areas. An alternative plain seal without brush seal to allow smoke detectors to be activated.
No routing is necessary, this seal can be fitted to door frames in minutes. Merely requires a 3.5mm or greater gap down the closing stile and across the door head. Fitted directly over hinges, no hinge bind and no gap necessary on hinge side. Once fitted the facing of the seal can be painted (the brush smoke seal must not be painted).
Application
Peel off backing paper from the self-adhesive fixing strip starting on the brush side and, with the smoke seal touching the door stop, press the intumescent seal into position. The seal can be easily cut with a sharp knife to fit around lock areas.
Two 1100mm lengths are supplied for fitting down the closing stile and these are 2.4mm thick. One 1000mm long x 2.4mm thick strip is supplied for the head of the door frame.
Two 1100mm long strips (1mm thick in standard version and 2.3mm thick in plastic version) are supplied for the back of the door frame, and these adhere from top to bottom, over the hinges (this helps to cool the hinges and screws in a fire).
Intumescent paper is supplied for application around a rebated lock, to cool the lock in a fire. Remove lock from door, cut Envirograf intumescent paper to size, wrap it around lock and sandwich it between the lock and door as you replace the lock. Also place paper under the keep plate.
Labels are supplied for single or double doors, printed “Fire Door – Keep Shut”.
These seals comply with BS476 Part 22. The intumescent seals can be painted or varnished over but the brush must not be painted. If the brush is accidentally painted over it can be easily replaced by ordering Envirograf Product 72 brush seals as replacements.
Note: panel pins are supplied to secure through the brush smoke seal at each end and every 300mm apart along its length. These panel pins must be fitted as requested by building control officers and fire officers.
Product Performance
Tested on old doors with head gaps up to 10mm, the SDS set sealed and expanded offering protection.
Tested to BS476 Part 22 (1987), achieving an integrity of up to 66 minutes.
BS476 Part 23 (1987).
Data Files and Downloads
Related Products
According to fire statistics, overheated light fittings and electrical faults are a leading cause o...
A water resistant and fire retardant intumescent adhesive. Designed with intumescent, thus providing...
Envirograf Under floor fire barrier UF60 (60 minutes) is made from graphite impregnated cloth covere...
A ready-mixed intumescent cement. On curing, the filler sets hard like normal cement but does not cr...
Water based clear or white intumescent coating kit for upgrading raised-and-fielded doors to fire do...